MA – DC chopper control strategy based on grid forming virtual machine coupling for HVDC systems

The DC chopper proved to be an essential component for offshore wind power grid access via HVDC by providing a reliable solution for dissipating excess wind energy during AC-faults at the onshore grid. When the DC voltage exceeds a certain threshold (typical range 3 -5 %), the DC chopper gets activated to maintain the DC voltage within safe limits by controlling the chopper current flowing through its resistors. In such arrangement, the onshore HVDC converter controls the DC voltage to maintain the energy balance and acts on the AC-side as a current source (grid following behavior).

The northern part of Germany is becoming a renewable energy hub with high wind power generation. Thus the importance of fast and reliable (inertial) frequency support in case of AC system split is gaining a high importance for the network operators.

With the recent development of grid forming (GFM) controls, fast (inertial) frequency support can be realized by emulating the behavior of the synchronous machine. For HVDC connections, the energy demand on one station is inherently coupled to the other HVDC station through the variation of the DC voltage. However, current offshore wind farms are passive systems which cannot provide inertial response as normal AC grid. The same limitation applies for providing ‘negative’ inertia during an overfrequency event in which transient power reduction is required from the offshore windfarm. Using the DC chopper for fast over-frequency limitation brings a huge benefit for the AC grid to limit the RoCoF at certain events. This requires however a fast and reliable trigger of the DC chopper in case of over-frequency event. Using the frequency measurement as input signal causes additional delays and might bring stability issues.

This thesis aims to develop an alternative method for frequency/angle support by triggering the DC chopper based on internal signals of the virtual machine rather than relying on frequency measurement of the grid voltage. Thermal capability limitations of the DC chopper must be considered to avoid long-term chopper activation or unrealistic over-dimensioning of the chopper. Based on an existing generic HVDC model in PSCAD with the control part modelled in Simulink and linked as Dynamic Library Link (DLL), the over-frequency limitation scheme utilizing the DC chopper will be implemented and analyzed. The existing model features on the offshore side a simple Voltage-frequency stiff controller to act as a slack for the passive offshore windfarm grid. The onshore side HVDC station, maintains the energy balance by controlling the DC voltage through the active current component, and simultaneously controlling the AC voltage through adjusting the reactive current reference. Since the focus of this model is on upper level control, the HVDC converter is modelled as a simple controlled 3-phase AC voltage source, while the DC chopper is modelled as a controlled DC current source.

The thesis comprises the following tasks: A literature review of existing methods for overfrequency limitation using a DC chopper. Development of a grid forming control scheme based on a virtual synchronous machine model for the onshore HVDC converter. The control shall allow maintaining the DC voltage during transients. Thus restrictions to the grid forming behavior applies. Verifying the grid forming behaviour by conducting relevant simulation cases with a Thevenin grid equivalent. Implementing existing methods for activation of the DC chopper based on frequency measurement as input and simulate overfrequency cases with simple test AC network. Development of an alternative method based on coupling the synchronous machine model parameters to the DC chopper activation logic. Performing comparative simulations between existing methods and the method/s developed in the thesis. Conclusion and summary of the findings.

Bearbeiter: Mohammad Alqudah

Betreuer: Dr. M. Suwan (Siemens Energy)

Frühest möglicher Beginn: sofort

Verantwortlicher: Prof. Dr.-Ing. Martin März